Woodward

MSLC-2

     

    Woodward’s Master Synchronizer and Load Control

     device_mslc-2.jpg

    Woodward’s MSLC-2™ functions with the DSLC-2™ control to provide synchronization and load control across Utility and Intertie breakers. The MSLC-2/DSLC-2 combination operates over an Ethernet communication network to control simple or complex generator system applications. This combination, 32 DSLC-2’s and 16 MSLC-2’s,  provide multiple unit, multiple segment, utility and intertie power management for complex power systems. Controls plant wide import/export levels while always providing bump-less load transfers with utility.

    The MSLC-2 control combines synchronization, dead bus closing, utility/intertie load sensor, baseload control, import/export control, VAR, power factor, and a master process control in one powerful package.
    The MSLC-2 provides phase matching or slip frequency synchronization, with voltage matching, across a utility or intertie breaker. The MSLC-2/DSLC-2 combination can handle multiple utility connections with a maximum of 8 bus segments in one application.

    The MSLC-2’s load sensor and load control sense true RMS power and provide a bump-less loading and unloading against a utility grid. Baseload, import/export, process, and utility unload modes control the KW power between different power sources at the same time controlling the reactive power, VAR and power factor.  Reactive power is also ramped on and off for the smoothest load transactions between power grids.

    The MSLC-2 communicates via Ethernet, with redundant Ethernet now available, to control real and reactive loading against the utility by DSLC-2 equipped generators.

    The tie breaker mode allows synchronization between multiple generator systems. Segments are connected and power can be measured across an intertie, but no load control is functional when in Tie breaker operation.

     Features include:

    • One MSLC-2 can provide master control for up to 32 DSLC and an additional 15 MSLC-2 in a system.
    • Two dedicated Ethernet lines for precise system communications between all DSLC-2’s and MSLC-2’s on the system.
    • Ethernet Modbus TCP for remote control and monitoring by PLC or DCS system.
    • Redundant Ethernet communications for enhanced reliability.
    • Master MSLC-2 redundancy, loss of communications with the designated MSLC-2 master initiates control hand off to the next designated MSLC-2 master.
    • The MSLC-2 hardware is adjustable for multiple applications.
    • Slip frequency or voltage phase matching synchronizing fully selectable with dead bus option in both directions provide full flexibility for intertie and main-tie-main applications.
    • Having functions integrated into one box eliminates the need for redundant sensors (like PTs, CTs, and MOPs) that connect to individual modules such as the load sensor and synchronizer.
    • Digital signal processing makes the MSLC-2 resistant to power line distortions and harmonics.
    • Three-phase true RMS power sensing provides accurate readings even with unbalanced phase loading and voltage fluctuations.
    • Export/import control over multiple utility MSLC-2’s in same segment.
    • The Woodward ToolKit™ software allows flexible setup using the same basic menu tree as the original MSLC plus an overview screen. No hand held programmer is required. Graphical overview of generators and bus bar parameters with trending makes the MSLC-2 commissioning friendly.
    • The Toolkit can be accessed either via one of the Ethernet ports or via RS-232 port.
    • Phase angle compensation provides adjustment for additional deviation correction across a transformer.
    • The system update feature allows for system reconfiguration.

     

     

    Specifications

    Power supply

    12/24 Vdc (8 to 40 Vdc)

    Consumption

    max. 15 W

    Ambient temperature (storage)

    -40 °C to 85 °C / -40 to 185 °F

    Ambient temperature (operation)

    -40 °C to 70 °C / -40 to 158 °F

    Ambient humidity

    95%, non-condensing

    Voltage AC input

    120 Vac and 480 Vac true RMS

    Accuracy

    Class 0.5

    Current AC input

    1A or 5A true RMS, galvanically isolated

    Accuracy Iac

    Class 0.5

    Discrete inputs (galvanically isolated)

    Range: 12/24 Vdc (8 to 40 Vdc)

    Relay outputs (galvanically isolated, potential free) 

    Relays, dry contacts

    Load (resistive)

    2A@24Vdc and 250 Vac

    Analog inputs (not isolated)

    0 to 500 Ohm, 0 to 20 mA

    Analog outputs (galvanically isolated)

    ± 10 V / ± 20 mA / PWM

    Housing

     

    Back panel mounting

    Sheet metal housing

    Dimension (WxHxD)

    250 × 227 × 84 mm

    Sealing

    IP20

    Weight

    Approx. 1,900 g

     

    Part Number

    MSLC-2 with 1A CT inputs 8440-1977
    MSLC-2 with 5A CT inputs 8440-1877
    Spare connector kit 8923-1806

    Applications

    application_mslc-2.gif

    Approvals

    CE.gif UL.gif cUL.gif GOST-R.gif CSA.gif LR.gif ABS.gif

     

    Documents

     Type

     Number

     DE

     EN 

     ES 

     FR

     IT

     PL

    Product Specification

    37494

                           

    Technical
    Manual

    37444

                           

    Guideform Specification

    37607

                           

     Go to the complete list of documentation:
      Search for all MSLC-2 Product Documentation
     

    Software:
      Configuration Software and Files